ABB · ACS880
An auxiliary fan fault has been detected; the auxiliary fan is not running. This compromises secondary cooling. The drive trips after a 2-minute suppression period during power-up, during which it only issues a warning. Continued operation without auxiliary cooling can lead to overheating.
Click steps to track your progress.
1. Power down and visually inspect the auxiliary fan for obstructions, then gently attempt to manually rotate the blades to check for binding.
2. With power on (and observing safety precautions), confirm that the auxiliary fan is not spinning and there are no abnormal noises.
3. Measure the DC voltage supplied to the auxiliary fan connector (e.g., 24VDC) at the drive's control board output.
4. Test the continuity of the wiring harness connecting the auxiliary fan to the drive's control board.
5. Replace the auxiliary fan unit with an equivalent manufacturer-specified part to ensure correct functionality.