ABB · ACS880
The memory within the drive's Power Unit has been cleared, indicating a loss of configuration or operational data. This internal fault requires expert diagnosis to restore functionality and prevent reoccurrence, as it affects the core logic of the power unit.
Click steps to track your progress.
Perform a full drive reset (e.g., parameter P9-01 = 1) and re-upload drive parameters from a saved backup file.
Verify the drive's internal battery (if equipped) for proper voltage (e.g., 3VDC lithium cell).
Check the drive's event log for preceding power supply faults or transients.
If parameter backup is unavailable, re-enter all parameters manually based on commissioning records.
Isolate the drive from potential EMI sources by improving grounding or shielding of control cables (per EN 61800-3).