There is a discrepancy between the drive's physical hardware identification and the information stored in its memory unit. This often occurs after maintenance such as a firmware update or memory unit replacement, potentially preventing the drive from operating correctly or safely.
Click steps to track your progress.
Perform a factory reset of the drive (e.g., parameter P9-01 = 1), then re-enter the power unit rating manually via parameter P0-01 (Drive Rating Code).
Verify the firmware versions of both the control unit and power unit are compatible (refer to drive manual).
If a control unit or memory module was recently replaced, ensure it is the correct part number for the power unit.
Re-upload parameters from a backup file after a factory reset.
Check for any physical damage or loose connections between the control board and the power unit sections of the drive.