ABB · ACS880
A short circuit has occurred within the brake chopper's IGBT, indicating a component failure that disables the regenerative braking function. This prevents the dissipation of excess energy, potentially leading to DC bus overvoltage and further drive damage if not addressed.
Click steps to track your progress.
Power off and lock out the drive. Visually inspect the brake chopper section of the drive for signs of burning, arcing, or damage to components.
Use a multimeter to measure continuity across the brake chopper's IGBT terminals (Collector-Emitter, Gate-Emitter) to detect internal shorts.
Check the DC link voltage (P7-05) before and during the fault condition (if possible to re-trigger safely) for overvoltage events.
Verify the drive's firmware version is current and compatible with the hardware.
If an external brake chopper, inspect its connections and internal components for damage.