ABB · ACS880
A fault has occurred in an external device connected to the drive's external event input 1. This general fault indicates a critical issue with peripheral equipment that the drive is monitoring and requires immediate attention. The drive will trip to protect itself or the process.
Click steps to track your progress.
1. Check the status of the external device (e.g., E-stop button, safety relay) connected to digital input DI1 for activation.
2. Measure the voltage level at drive terminal DI1 (relative to GND) to confirm the input signal state (e.g., 24VDC for active, 0VDC for inactive).
3. Perform a continuity test on the wiring from the external device's output contacts to the drive's DI1 terminal.
4. Review parameter P4-01 'DI1 function' to verify that the configured input type matches the connected external device's function.
5. If a safety circuit, verify the status of any associated safety relay (e.g., K1) and its output contacts feeding DI1.