ABB · ACS880
A fault has occurred in an external device connected to the drive's external event input 2. This general fault indicates a critical issue with peripheral equipment that the drive is monitoring and requires immediate attention. The drive will trip to protect itself or the process.
Click steps to track your progress.
1. Identify the specific external device connected to digital input DI2 (e.g., via electrical schematics) and check its operational status.
2. Use a multimeter to measure the voltage at drive terminal DI2 (relative to GND) to confirm the signal status from the external device.
3. Inspect the cable run from the external fault device to the drive's DI2 terminal for integrity and secure connections.
4. Temporarily bypass the external fault device by disconnecting its wire from DI2 and connecting DI2 directly to 24VDC (if N.O.) or 0VDC (if N.C.) to test the input circuit.
5. Confirm parameter P4-02 'DI2 function' is correctly assigned for the intended external fault monitoring.