ABB · ACS880
One or more of the brake resistor data settings (parameters 43.08 … 43.10) are incorrect or missing. This prevents the drive from correctly calculating brake resistor operation and protection. Incorrect data can lead to improper braking or resistor damage.
Click steps to track your progress.
Retrieve the nameplate data from the physically installed brake resistor for its nominal resistance (Ohms) and rated power (Watts).
Enter the correct nominal resistance value into drive parameter `P43.08` (Brake resistor resistance).
Enter the correct rated power value into drive parameter `P43.09` (Brake resistor power).
Verify the brake chopper activation voltage `P43.10` (Brake chopper ON voltage) is set to a reasonable value, typically `700VDC` for a `400V` class drive.
If parameters were previously saved, try reloading a known-good parameter set from a PC tool (e.g., `DriveManager`).