ABB · ACS880
Warning generated by edge counter 2, indicating that a specific number of events (edges) has been detected or a threshold has been crossed. This is typically used for monitoring operations, component life, or sequence integrity. Ignoring this could lead to unexpected behavior or component failure if a limit is exceeded.
Click steps to track your progress.
Identify the specific process or component whose events are being tracked by Edge Counter 2 by reviewing parameter descriptions and system programming.
Note the current accumulated count from parameter P4-06.00 (Current Edge Count 2).
Perform any preventative maintenance or operational review triggered by the attainment of this event count.
Reset Edge Counter 2 to zero by setting parameter P4-06.02 (Reset Counter 2) to '1' (Execute) once the necessary actions are complete.
Modify the limit value in parameter P4-06.01 (Edge Count 2 Limit) if the event threshold requires adjustment.