ABB · ACS880
A fault has occurred in an external device connected to the drive's external event input 1. This general warning indicates an issue with peripheral equipment that the drive is monitoring. The drive continues to operate, but the external device needs attention.
Click steps to track your progress.
Identify the external device connected to drive digital input DI1 (via parameter P5-01 'DI1 function').
Measure the voltage at drive terminal DI1. If configured as active low, confirm 0VDC; if active high, confirm 24VDC (or configured voltage).
At the external device identified, verify its operational status and output contact state (e.g., check E-stop button position).
Inspect the wiring between the external device's output contact and drive terminal DI1 for continuity and secure connections.