A fault has occurred in an external device connected to the drive's external event input 2. This general warning indicates an issue with peripheral equipment that the drive is monitoring. The drive continues to operate, but the external device needs attention.
Click steps to track your progress.
Identify the external device connected to drive digital input DI2 (via parameter P5-02 'DI2 function').
Check the status LEDs or display on the external device (e.g., overload relay) to confirm its operational state.
Measure the voltage at drive terminal DI2 and compare it to the expected state (e.g., 24VDC for active, 0VDC for inactive).
Trace the wiring from the external device to drive terminal DI2, inspecting for physical damage or loose terminals.