EL
ErrorLib
Brands
||
  1. Home
  2. Allen-Bradley
  3. 160
  4. 41
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

41

UV Short Fault

Allen-Bradley · 160

What does 41 mean?

This fault indicates that excessive current has been detected between the 'U' and 'V' output terminals of the controller. This is typically caused by a short circuit either within the motor windings themselves or in the external wiring connecting the controller to the motor. This is a critical fault that can cause immediate and severe damage to the controller's inverter section.

Common Causes

  • Phase-to-phase short circuit between the U and V conductors in the motor cable.
  • Internal short circuit between the U and V phase windings within the motor.
  • Damage or foreign material on the output terminal block (U and V) of the controller, creating a conductive path.
  • Insulation breakdown within the motor resulting in a direct U-V winding short.
  • Sudden, severe mechanical overload causing instantaneous motor winding damage leading to a short.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Immediately disconnect the motor from the controller's U, V, W output terminals.

  2. 2

    2. Measure the resistance between the U and V terminals of the motor cable using an ohmmeter (cable disconnected from both controller and motor).

  3. 3

    3. Measure the resistance between the U and V motor winding terminals (motor disconnected from cable) using an ohmmeter. Compare to expected motor winding resistance.

  4. 4

    4. Inspect the controller's U and V output terminals and the corresponding motor cable lug connections for signs of arcing, carbon tracking, or debris.

  5. 5

    5. Perform a hipot test (AC or DC) between the U and V conductors of the motor cable to confirm insulation integrity, following safety procedures.

Browse all codes in this manual (18)
Verified technical data. Last updated: April 2026

Related Faults

03Power Loss Fault04Under Voltage Fault05Over Voltage Fault
Source: Allen-Bradley 160
View Official PDFSearch more codes in this manual