08

Over Temperature Fault

Allen-Bradley · 160

What does 08 mean?

This fault indicates that the controller's internal temperature, typically measured at the heatsink, has exceeded its safe operating limit. This is often caused by insufficient cooling. Prolonged operation at high temperatures can severely degrade the lifespan of the controller's electronic components.

Common Causes

  • Blocked or dirty heatsink fins and cooling fan obstructing airflow within the controller enclosure.
  • Ambient temperature around the controller exceeding its maximum specified operating limit (e.g., >40 degrees Celsius).
  • Degraded or failed cooling fan within the controller, reducing airflow over the heatsink.
  • Installation of the controller in an enclosure that is too small or lacks adequate ventilation (e.g., fan, exhaust filters).
  • Continuous operation at or above the controller's rated current for extended periods in high ambient temperatures.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Inspect controller heatsink fins and cooling fan for dust, dirt, or obstructions. Clean thoroughly using compressed air (non-conductive) or a soft brush.

  2. 2

    2. Verify the cooling fan's operation by visual inspection and listening for fan noise. Measure its voltage supply (e.g., 24V DC or 120V AC) if it's not running.

  3. 3

    3. Measure the ambient temperature inside the electrical enclosure at the controller's location using a digital thermometer. Ensure it is below the controller's specified max operating temp.

  4. 4

    4. Ensure adequate ventilation in the electrical enclosure by checking filter cleanliness and verifying proper operation of enclosure cooling fans or air conditioners.

  5. 5

    5. Reduce the controller's output current (e.g., by reducing motor load or decreasing carrier frequency P4-01) if continuous operation at high loads is leading to overheating.

Browse all codes in this manual (18)
Verified technical data. Last updated: March 2026

Related Faults