Max Retries Fault
Allen-Bradley · 160
What does 33 mean?
This fault occurs when the controller has failed to successfully reset a previous fault condition within the maximum number of attempts defined by parameter P50 – [Restart Tries]. This indicates an underlying persistent issue that cannot be automatically cleared.
Common Causes
- The underlying fault condition (e.g., overcurrent, undervoltage) is persistent and not being resolved by the controller's auto-restart attempts.
- Parameter P50 (Restart Tries) is set too low for an intermittent fault, leading to a lockout after too few attempts.
- Incorrect configuration of auto-restart delay (e.g., P51) causing subsequent restart attempts to fail.
- A transient fault condition that recurs immediately upon restart, preventing successful operation.
- Severe mechanical issue or power supply instability that consistently triggers a fault.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Identify the LAST fault code that occurred PRIOR to the 'Max Retries Fault' (e.g., from the fault history log). Troubleshoot that specific fault first.
- 2
2. Increase the value of parameter P50 (Restart Tries) to allow more attempts for transient faults to clear, if appropriate for the application.
- 3
3. Adjust parameter P51 (Restart Delay) to provide sufficient time for the system to stabilize before the next restart attempt.
- 4
4. Monitor critical system parameters (e.g., motor current, DC bus voltage) during restart attempts to pinpoint why the underlying fault is recurring.
- 5
5. Review the application for any intermittent mechanical issues, load fluctuations, or power supply anomalies that repeatedly trigger faults.