I.Ptxx.ShortCircuit

Safety Output Point Short Circuit Tag Active

Allen-Bradley · Compact 5000 Digital I/O Modules

What does I.Ptxx.ShortCircuit mean?

This tag indicates that a short circuit has been detected on a Safety Output point (Ptxx). This can occur when the output is shorted to 24V DC, to ground, or between output points in a pair. When active, the module faults and turns off the affected output.

Common Causes

  • Output point Ptxx wiring shorted to 24V DC due to insulation breakdown or incorrect connection.
  • Output point Ptxx wiring shorted to system ground due to insulation breakdown or contact.
  • Output points in a pair (e.g., Ptxx and Ptxx+1) shorted to each other.
  • Damage to the field wiring or the connected load causing a low-resistance path.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Identify the specific output point Ptxx where the fault is detected via Studio 5000 Logix Designer diagnostics.

  2. 2

    Examine the physical wiring connected to output point Ptxx for any damage, improper termination, or contact that could cause a short to 24V DC or system ground.

  3. 3

    With power removed from the module and field devices, use a multimeter to measure resistance between the output terminal Ptxx and 24V DC, and between Ptxx and system ground; expect an open circuit (high resistance).

  4. 4

    If the output point is part of a paired output, measure resistance between the two output terminals of the pair to check for a short.

  5. 5

    If the short circuit was to 24V DC, cycle power to the entire module to reset the diagnostic.

Browse all codes in this manual (38)
Verified technical data. Last updated: April 2026