Allen-Bradley · Compact 5000 Digital I/O Modules
This diagnostic is triggered on a 5069-IB8S or 5069-IB8SK module's test output point. It occurs under specific conditions related to muting lamp operation, typically when a short circuit is detected while the test output is configured for Muting Lamp mode and commanded ON. The I/O Status Indicator will flash red.
Click steps to track your progress.
Disconnect the muting lamp and any associated wiring from the affected test output terminal.
Measure resistance at the test output terminal to 24VDC, other test output points, and protective earth ground — expect high resistance (open circuit).
Verify the muting lamp device is correctly wired and not internally shorted.
In the Studio 5000 Logix Designer application, check parameters for 'Muting Lamp Points' (e.g., Point 02, Point 03) and 'Test Output Point Mode' (should be 'Muting Lamp').