Allen-Bradley · Compact 5000 Digital I/O Modules
This diagnostic indicates an output short circuit or overcurrent fault condition exists on an output point. For 5069-IB8S/IB8SK modules, this protection prevents damage to test outputs. When detected, the output faults and turns off, and the I/O Status Indicator flashes red.
Click steps to track your progress.
Disconnect the load from the affected output terminal.
Use a multimeter to measure resistance between the output terminal and 24VDC, other output terminals, and protective earth ground — expect high resistance (open circuit).
Inspect all physical wiring connected to the affected output for signs of insulation breakdown, mechanical damage, or incorrect connections.
If wiring is clear, test the load device for internal shorts by measuring its resistance.