ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

ShortCircuitGround

Short Circuit to Ground

Allen-Bradley · Compact 5000 Digital I/O Modules

What does ShortCircuitGround mean?

This diagnostic indicates that a short circuit to ground condition exists on an output point. This means the output wiring or the connected load has inadvertently made contact with the protective earth ground or a grounded enclosure. The tag automatically resets to 0 when the condition is removed.

Common Causes

  • Output wiring insulation breakdown, causing contact with a grounded surface or enclosure
  • Internal fault within the load device causing its output terminal to short to ground
  • Incorrect wiring where the output terminal is directly connected to ground

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect the load from the affected output terminal.

  2. 2

    Use a multimeter to measure resistance between the output terminal and protective earth ground — expect a very high resistance (open circuit).

  3. 3

    Visually inspect all physical wiring associated with the affected output for damaged insulation or contact with grounded components.

Browse all codes in this manual (38)
Verified technical data. Last updated: April 2026

Related Faults

CIPSyncTimeoutCIP Sync Master TimeoutConnectionFaultedOwner-Controller Connection FaultCriticalTemperatureModule Critical Temperature
Source: Allen-Bradley Compact 5000 Digital I/O Modules
Open Manual (Page 152)Search more codes in this manual