Allen-Bradley · Logix 5000 Controllers
This specific code identifies a major recoverable fault, indicating that the controller's internal temperature has exceeded its defined major fault threshold. The fault is recorded in the major fault log and displayed on the front panel as 'T17:C34 CPU Temperature Fault'. If the fault is not cleared by a fault handler in the user program, the module will transition into fault mode.
Click steps to track your progress.
Examine the major fault log for specific timestamp and conditions leading to T17:C34
Review the application logic for any configured fault handlers and verify their functionality to clear T17:C34
Measure the ambient temperature within the control panel enclosure using a calibrated thermometer
Visually inspect controller heatsinks and cooling vents for dust accumulation or obstructions
Verify the operational status of any enclosure cooling fans or air conditioning units, confirming proper setpoints