Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

14-1

Safety Task watchdog expired

Allen-Bradley · Logix 5000

What does 14-1 mean?

The safety task has not completed within its specified period of time. This can be due to a program error causing an infinite loop, the program's complexity exceeding execution speed, a higher priority task blocking it, or the safety partner being removed.

Common Causes

  • User task not completed in specified period of time
  • Program error caused an infinite loop
  • Program is too complex to execute as quickly as specified
  • Higher priority task is keeping this task from finishing
  • Safety partner has been removed

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Clear the fault.

  2. 2

    If a safety task signature exists, safety memory is re-initialized and the safety task begins executing.

  3. 3

    If a safety task signature does not exist, re-download the program to allow the safety task to run.

  4. 4

    Reinsert the safety partner, if it was removed.