F016

Scanner not available for 1771 rack adapter

Allen-Bradley · Logix 5000

What does F016 mean?

The scanner is not available to communicate with a 1771 rack adapter. This disrupts I/O communication with the specified rack.

Common Causes

  • The scanner is not available to communicate with a 1771 rack adapter

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure supply voltage at the 1771 rack adapter's power input terminals against specified nominal voltage.

  2. 2

    Inspect the RIO (Remote I/O) cable connecting the Logix 5000 system to the 1771 rack adapter for damage and secure connections at both ends.

  3. 3

    Verify the RIO configuration parameters within the Logix 5000 program (e.g., rack number, baud rate, module type) match the physical 1771 rack adapter settings (e.g., DIP switches).

  4. 4

    Observe the status indicator LEDs on the 1771 rack adapter for any fault or communication errors, referring to the adapter's manual for interpretation.

  5. 5

    Inspect the 1771 rack adapter for proper seating in its slot within the 1771 chassis, ensuring all backplane connectors are fully engaged.