Allen-Bradley · MicroLogix 1400 Programmable Controllers
DNP3 10K events are enabled simultaneously with Recipe/Data Log functionality in the user program. This is a non-user fault, indicating an unsupported configuration combination within the controller's firmware that prevents both features from operating concurrently.
Click steps to track your progress.
Remove Recipe/Data Log configuration from the user program when the DNP3 10K events bit (S:36/11) is set, then reload and enter Run mode.
Alternatively, clear the DNP3 10K events bit (S:36/11) in the user program if Recipe/Data Log functionality is prioritized, then reload and enter Run mode.