EL
ErrorLib
Brands
||
  1. Home
  2. Allen-Bradley
  3. PowerFlex 520-series Adjustable Frequency
  4. F043
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

F043

Phase VW Short

Allen-Bradley · PowerFlex 520-series Adjustable Frequency

What does F043 mean?

Excessive current has been detected between the drive's V and W output terminals, indicating a short circuit. This could be a phase-to-phase short in the motor windings or within the cables connecting the drive to the motor. This is a critical fault that can cause severe damage to the drive's output power stage (IGBTs) if not immediately addressed.

Common Causes

  • Short circuit between V-phase and W-phase conductors within the motor power cable due to insulation damage, such as crushing or severe bending.
  • Internal short circuit between V and W windings inside the motor, typically caused by insulation failure from continuous overload or winding contamination.
  • Arcing or tracking path established between V-phase and W-phase terminals due to moisture, dust, or conductive foreign material.
  • Manufacturing defect in the motor windings leading to an inter-phase insulation breakdown between V and W phases.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect the motor leads (U, V, W) from the drive output terminals (T1, T2, T3).

  2. 2

    Measure the resistance between the V-phase and W-phase motor leads using a multimeter. A reading significantly below the expected winding resistance indicates a short.

  3. 3

    Visually inspect the motor cable for physical damage, particularly focusing on areas subject to strain or impact.

  4. 4

    Inspect the motor terminal box for any signs of arcing, tracking, or conductive bridging material between V and W terminals.

  5. 5

    If the motor cable is suspected, disconnect the cable from the motor and measure resistance between V and W conductors at the drive end.

  6. 6

    If the motor windings are shorted, schedule motor removal for repair or replacement.

Browse all codes in this manual (48)
Verified technical data. Last updated: April 2026

Related Faults

F000No FaultF002Auxiliary InputF003Power Loss
Source: Allen-Bradley PowerFlex 520-series Adjustable Frequency
View Official PDFSearch more codes in this manual