Allen-Bradley · PowerFlex 520-series Adjustable Frequency
Control through the drive's embedded EtherNet/IP adapter has been interrupted. This signifies a loss of communication between the drive and its EtherNet/IP master controller or PLC, resulting in the loss of remote command and control capabilities and potentially triggering a fault or shutdown.
Click steps to track your progress.
Verify the Ethernet cable connection to the drive's embedded EtherNet/IP port (RJ45) and the network switch/PLC is secure and undamaged.
Check the link/activity LEDs on the drive's Ethernet port and the connected network switch port; they should indicate link presence and activity.
Confirm the EtherNet/IP master controller (PLC) is running and configured to communicate with the drive; check PLC I/O tree and diagnostics.
Verify the drive's IP address (P9-29), Subnet Mask (P9-30), and Gateway (P9-31) settings match the network topology using DriveTools SP or HMI.
Ping the drive's IP address from a computer on the same subnet to confirm network layer connectivity.
If the problem persists and network connectivity is confirmed, consider performing a firmware update or, if hardware failure is suspected, drive replacement.