100

Parameter Chksum

Allen-Bradley · PowerFlex 750

What does 100 mean?

The checksum read from the non-volatile storage does not match the checksum calculated, indicating a potential corruption in the drive's stored parameters. The data is automatically set to default values, leading to loss of configured settings. This can result in incorrect drive operation and requires re-commissioning if not properly addressed.

Common Causes

  • Sudden power loss or brownout event occurring during a critical parameter write operation to non-volatile storage.
  • Electromagnetic interference (EMI) or voltage transients corrupting data integrity within the non-volatile memory.
  • Internal hardware fault or degradation of the non-volatile memory (e.g., EEPROM, Flash) chip on the main control board.
  • Incomplete or corrupted firmware update that affects the parameter storage structure.
  • Incorrect parameter upload from a backup file with a different firmware version.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Perform a drive power cycle by disconnecting input power (e.g., 480VAC) for 30 seconds, then reapplying.

  2. 2

    2. Upload a known good parameter backup file from a PC or HMI memory module using the drive's programming software.

  3. 3

    3. If no backup exists, manually re-enter all critical motor and application parameters as per commissioning documentation.

  4. 4

    4. Verify the stability of the incoming AC supply voltage and proper grounding for the drive system (e.g., checking ground resistance at less than 1 ohm).

  5. 5

    5. If the fault persists after re-entering parameters, replace the main control board (MCB) as the non-volatile memory may be damaged.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

101PwrDn NVS Blank10132I1 Incompat PS10134I1 UBrd Fault
Source: Allen-Bradley PowerFlex 750
View Official PDFSearch more codes in this manual