Beckhoff · AX5000 Servo Drive
This error indicates a problem with the Service over EtherCAT (SoE) communication parameters configured for the drive. The specific parameter causing the fault is identified in S-0-0021, which can be viewed in the TCDriveManager Diagnostics window. A common root cause is an incorrect setting in parameter P-0-0150, particularly an improper value for "Signal periods per rotation." This error often triggers other consequential errors like F152 and FA01, preventing the drive from operating correctly.
Click steps to track your progress.
Read parameter S-0-0021 to identify the specific SoE parameter (index and subindex) causing the error.
Compare the identified parameter's value and data type in the drive's configuration (via service tool) with the value sent by the EtherCAT master.
Verify the EtherCAT network topology and cabling for proper connection and shielding. Check LED indicators on the drive's EtherCAT ports (e.g., LINK/ACT).
Perform a drive factory reset (P-0-0000=1) and reload the drive configuration from a known good backup file.
Update drive firmware and EtherCAT master firmware to compatible versions as per manufacturer's guidelines.