Beckhoff · TwinSAFE Logic FB
The input value (InValue) has expired, and its current state is above zero. This suggests that the input signal has either become invalid or has risen above its expected range, leading to a safety state. The fault provides the FB instance, the current InValue, and the MaxAllowedValue for detailed diagnosis.
Click steps to track your progress.
1. Measure the voltage or current at the analog input terminals (e.g., AI_B) of the safety module.
2. Verify the sensor's output (e.g., 4-20mA, 0-10V) directly at the sensor terminals.
3. Check the scaling and offset parameters (e.g., P3-03, P3-04) in the TwinSAFE configuration for the analog input.
4. Inspect the input signal wiring for short circuits to an external voltage or incorrect termination.
5. Replace the sensor if its output remains above the valid range even when the process value is acceptable.