Beckhoff · TwinSAFE Logic FB
The 'MaxTimeExpired' flag within the FB Envelope function block is TRUE. This confirms that the maximum permissible time for the safety function output to be active has been reached, causing the output to switch off. This fault prioritizes safety by ensuring the output does not remain active beyond its design limit.
Click steps to track your progress.
1. Identify the specific safety function output that remained active and the condition that caused it.
2. Review the configured 'Max Time' parameter (e.g., P5-01) in the TwinSAFE logic for appropriateness against process requirements.
3. Verify the physical state and operation of all safety inputs (e.g., light curtain, safety switch at terminal S1-1) associated with the safety function.
4. Check all output conditions and interlocks that are designed to clear the safety function's active state.
5. Monitor the relevant process variables and safety inputs in real-time to observe the timing of events.