Beckhoff · TwinSAFE Logic FB
A general error related to the input value (InValue) has occurred within the FB Envelope function block. This could be due to invalid input data, a fault in the input signal path, or internal processing issues. This fault will lead to the FB entering a safe state, halting operation.
Click steps to track your progress.
1. Monitor the raw 'InValue' in the TwinCAT System Manager (or equivalent diagnostic tool) for erratic or out-of-range readings.
2. Measure the voltage or current directly at the analog input terminals (e.g., AI_01) on the safety I/O module to confirm signal integrity.
3. Verify the sensor's health and output (e.g., 4-20mA, 0-10V) at its terminals.
4. Check the configuration of the analog input module (e.g., EL3102, channel 1) for correct input range and scaling parameters.
5. Power cycle the safety I/O module (e.g., EL3xxx) to reset its internal diagnostics.