FB ESTOP Bit 3

E-Stop Discrepancy Error - Input Group 4

Beckhoff · TwinSAFE Logic FB

What does FB ESTOP Bit 3 mean?

A discrepancy has been detected between the two channels of input group 4 for the FB ESTOP. This indicates that the redundant E-Stop input signals are not in agreement, suggesting a potential failure of one channel, a wiring issue, or an incorrect switching sequence. This will prevent the E-Stop function from operating safely and halt the machine.

Common Causes

  • A wiring fault (e.g., open circuit or short to ground) on one channel of the E-Stop input for Group 4.
  • Mechanical binding or debris preventing one side of the E-Stop button's redundant contacts from operating freely.
  • High resistance in one of the cable conductors supplying the E-Stop input, causing a voltage difference across channels.
  • Input filtering parameters (e.g., P_INPUT_FILTER_G4) set too aggressively, ignoring legitimate input changes.
  • Faulty E-Stop switch, where one redundant contact is intermittently failing to make proper connection.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    De-energize and check the resistance of both redundant E-Stop input lines from the device to the controller (e.g., from E-Stop button to terminals X4.1 and X4.2).

  2. 2

    Verify the physical operation of the E-Stop button for Input Group 4, ensuring both contacts actuate smoothly and simultaneously.

  3. 3

    Measure the voltage level on both E-Stop input channels at the safety controller during both active and inactive states.

  4. 4

    Inspect all connections for Input Group 4, ensuring terminal screws are tightened to specified torque and no corrosion is present.

  5. 5

    Temporarily increase the discrepancy time parameter (e.g., P_DISC_TIME_G4) in the safety controller to rule out rapid asynchronous switching as the cause.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

0x401FPress Not Moving After Start Command0x4020Press Unexpectedly Stopped After Starting0x4021Insufficient Press Movement
Source: Beckhoff TwinSAFE Logic FB
View Official PDFSearch more codes in this manual