FB MON Bit 0

Monitoring Discrepancy Error - Input Group 1

Beckhoff · TwinSAFE Logic FB

What does FB MON Bit 0 mean?

A discrepancy has been detected between the channels of input group 1 in the FB MON function block. This means the redundant inputs are not switching in sync or are reporting different states, indicating a potential sensor fault, wiring issue, or incorrect timing that could compromise the monitoring function, leading to a safety stop.

Common Causes

  • One channel of a monitored redundant safety input device (e.g., safety gate switch S1-S2) is stuck open or closed.
  • Broken conductor or loose terminal connection on one channel (e.g., input MonIn_CH1) of the monitored safety device.
  • Asynchronous switching of the redundant contacts within a safety device due to mechanical wear or sticky contacts.
  • Electrical noise or transient voltage spikes on one input channel causing a momentary discrepancy.
  • Input synchronization time parameter (e.g., P_MON_DISC_TIME_G1) set too short for the specific safety device's characteristics.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Actuate the monitored safety device (e.g., open/close safety gate) and observe the corresponding input LEDs (e.g., IN_G1_A, IN_G1_B) on the safety controller for synchronized state changes.

  2. 2

    Measure continuity across both redundant output contacts of the safety device (e.g., between terminals 3 and 4, and 5 and 6 of a safety interlock switch) in both states.

  3. 3

    Check resistance of individual wire runs from the safety device output terminals to the safety controller input terminals (e.g., from safety switch 3 to controller MonIn_CH1).

  4. 4

    Increase the discrepancy time parameter (e.g., P_MON_DISCREPANCY_DELAY_G1) in the safety controller configuration if inputs are switching asynchronously but within acceptable limits.

  5. 5

    Verify that the monitored device (e.g., safety light curtain OSSD outputs) has stable power supply and is not experiencing internal faults.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026