FB MUTING Bit 9

OSSD Input Discrepancy Not Reset

Beckhoff · TwinSAFE Logic FB

What does FB MUTING Bit 9 mean?

A discrepancy error in 'OssdIn1'/'OssdIn2' was detected and has not yet been acknowledged or reset. This indicates a persistent underlying issue with the OSSD input group that needs active resolution and acknowledgment before normal operation can resume. The system will remain in a safe, stopped state.

Common Causes

  • The initial discrepancy condition in 'OssdIn1'/'OssdIn2' (from ref=37) has not been rectified.
  • Faulty wiring or signal integrity issue on the external reset input line for the muting function (e.g., input X1.6).
  • Persistent malfunction of the safety light curtain's OSSD outputs, continuously sending inconsistent signals.
  • Improperly configured reset logic within the safety PLC for the muting function block.
  • Residual electrical charge or ground fault impacting the OSSD input lines, preventing proper signal stabilization.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Thoroughly investigate and correct the root causes of 'Muting Discrepancy Error - OSSD Input Group' (ref=37), focusing on light curtain status and OSSD wiring.

  2. 2

    2. Verify the functionality of the designated reset button or HMI command and confirm its corresponding input signal (e.g., X1.6) reaches the safety controller.

  3. 3

    3. Use an oscilloscope to verify that both OSSD input signals (OssdIn1, OssdIn2) are stable and synchronized at the safety PLC terminals.

  4. 4

    4. Check the configuration of the FB MUTING function block in the safety program, specifically verifying the reset conditions and parameters.

  5. 5

    5. Temporarily disconnect and then reconnect the OSSD inputs to the safety PLC terminals (X2.1, X2.2) to ensure no residual electrical issues are present, then perform a reset.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026