Beckhoff · TwinSAFE Logic FB
A discrepancy has been detected within the two channels of input pair 2 for the FB TWOHAND. This means the redundant hand actuation signals are not synchronizing correctly, indicating a potential issue with the two-hand device, its wiring, or incorrect timing. This will prevent safe two-hand operation and put the machine into a safe state.
Click steps to track your progress.
1. Power down the safety system, then use a multimeter to measure the resistance of the wiring from each button of input pair 2 to its respective safety input terminal (e.g., X5.1, X5.2).
2. With power restored, observe the diagnostic LEDs on the safety module for input pair 2 while actuating each button independently and simultaneously.
3. Replace the push button switch assembly for input pair 2 if its internal contacts show resistance instability or failure during actuation tests.
4. Inspect the shielded cabling for input pair 2; verify the shield is properly grounded at one end (e.g., control cabinet ground bar).
5. Access the safety controller's programming interface and temporarily increase the 'TwoHandDiscTime' parameter (e.g., to 500ms) to rule out overly sensitive timing.