Beckhoff · TwinSAFE Logic FB
A discrepancy has been detected between the actuation times of input pair 1 and input pair 2 for the FB TWOHAND. This means the operator is not actuating both hands simultaneously within the allowed time window, or there's an issue with the timing of the two-hand control device itself. This fault ensures true simultaneous actuation for safety and stops the machine.
Click steps to track your progress.
1. Observe the operator's hand placement and simultaneous actuation technique, providing retraining if necessary to ensure both buttons are pressed concurrently.
2. Measure the actuation and release times of each two-hand button assembly using a timing device or oscilloscope connected to the input terminals (e.g., X5.1 and X5.3).
3. Access the safety controller's programming interface and adjust the 'BetweenPairDiscTime' parameter (e.g., increase from 200ms to 350ms) to accommodate operator variance.
4. Verify the integrity of the 24VDC supply voltage to both two-hand button assemblies, checking for drops below 22VDC during actuation.
5. Check and clean the electrical contacts within both two-hand button assemblies for any foreign material that could impede consistent response.