Beckhoff · TwinSAFE Logic FB
Similar to 'FB TWOHAND Bit 1', but specifically when the 'Safe Inputs after Disc Error' option is active for input pair 2. This means a discrepancy occurred, and although the FB is attempting to maintain a safe state for the inputs, the error persists, indicating a critical issue with the input pair that requires immediate attention and prevents operation.
Click steps to track your progress.
1. Verify secure connections at all terminals for input pair 2, from the buttons to the safety input module (e.g., X5.1, X5.2).
2. Actuate the buttons for input pair 2 and use a multimeter to verify consistent voltage levels (e.g., 24VDC active) at the respective safety input terminals.
3. Isolate and test the individual pushbuttons for input pair 2 for proper contact operation (NO/NC state changes) using a continuity tester.
4. If suspected EMI, ensure signal cables for input pair 2 are routed away from power cables and proper shielding is maintained.
5. After addressing the discrepancy, perform a forced safety system reset (e.g., acknowledge fault via HMI or dedicated input) to clear the 'Safe Inputs Active' state.