Beckhoff · TwinSAFE Logic FB
At least one TwinSAFE connection within the EL/EJ69x0 group is faulty. This implies a disruption or loss of communication between safety devices or across the EtherCAT network for safety-relevant data. This will prevent safe operation and necessitate immediate investigation of network integrity, as safety communication is compromised.
Click steps to track your progress.
1. Check the EtherCAT network diagnostics in TwinCAT System Manager for topology errors, lost frames, or disconnected devices.
2. Inspect all EtherCAT patch cables and connectors in the safety network segment for damage or secure connections.
3. Verify the FSoE connection watchdog time parameter (e.g., P7-03) and connection IDs for consistency across all TwinSAFE devices.
4. Power cycle the affected TwinSAFE modules (e.g., EL69x0, EL1957) and the EtherCAT coupler.
5. Ensure the EtherCAT master is stable and not experiencing its own communication issues (e.g., network adapter driver problem).