Beckhoff · TwinSAFE Logic FB
A timeout has elapsed while waiting for a communication error in 'passivate' mode of a manual control unit. This suggests a problem with the deactivation sequence or communication with the manual control unit, potentially preventing the system from entering a safe passive state correctly. The system will remain in an unsafe or error state.
Click steps to track your progress.
1. Verify the communication link (e.g., EtherCAT, FSoE) to the manual control unit using TwinCAT diagnostics.
2. Check the status and power supply of the manual control unit to ensure it is operational and responsive.
3. Inspect the wiring and connectors (e.g., X201) to the manual control unit for damage, loose connections, or incorrect termination.
4. Adjust the 'Deactivation Timeout' parameter (e.g., P9-01) in the TwinSAFE configuration if the process requires a longer response time.
5. Review the manual control unit's diagnostic messages or internal logs for communication errors.