Beckhoff · TwinSAFE Logic FB
The TwinSAFE logic program was unexpectedly restarted because the EtherCAT connection was restarted or a user logged in without reloading the TwinSAFE logic program (or parts of it). This can lead to an inconsistent or unsafe state if the logic program's state is not properly re-initialized, requiring a safety shutdown.
Click steps to track your progress.
1. Ensure the EtherCAT master (e.g., industrial PC) is stable and not experiencing unexpected restarts.
2. Always perform a full 'Activate Configuration' and 'Write to Flash' for the TwinSAFE project after any changes or restarts.
3. Check the EtherCAT network for intermittent disconnections (e.g., faulty cables, loose connectors).
4. Review the TwinCAT System Manager logs for any messages related to EtherCAT master restarts or configuration changes.
5. Perform a complete power cycle of the EL/EJ69x0 module and then reload the TwinSAFE logic program.