F2009

PL Load parameter default values

Bosch Rexroth · IndraDrive MPx02

What does F2009 mean?

This non-fatal error signifies that a command to load default parameter values has been initiated or executed on the IndraDrive MPx02, typically indicated by 'PL' in the display. While not a fault in itself, it signals a significant change in drive configuration, potentially overriding custom settings.

Common Causes

  • Manual command to load default parameters via HMI or software.
  • Automatic loading of default parameters due to detection of corrupt or invalid stored parameters.
  • Firmware update that required a parameter reset to defaults.
  • Improper storage of non-volatile parameters, forcing the drive to revert to defaults.
  • Initial startup of a new or factory-reset IndraDrive MPx02.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Confirm whether loading default parameters was an intentional action. If so, re-commission the drive with the correct application-specific parameters.

  2. 2

    If unintentional, check the parameter history or event log to determine why the defaults were loaded.

  3. 3

    Reload a previously saved, application-specific parameter set to restore the drive's custom configuration.

  4. 4

    Verify the integrity of the drive's non-volatile memory or storage medium (e.g., MMC) to prevent future data loss.

  5. 5

    Perform a full drive configuration backup after correctly setting all parameters.