F2836

DC bus balancing monitor error

Bosch Rexroth · IndraDrive MPx02

What does F2836 mean?

An error has been detected by the DC bus balancing monitor. This system ensures that the voltage across series-connected DC bus capacitors remains balanced. An imbalance can indicate a faulty capacitor, a problem with the balancing resistors, or an issue with the monitoring circuit itself, potentially leading to capacitor overvoltage and failure.

Common Causes

  • Defective DC bus capacitor (e.g., increased ESR)
  • Faulty balancing resistors across DC bus capacitors
  • Problem with the DC bus voltage measurement circuitry
  • Interference affecting the balancing monitor's readings
  • Internal hardware fault in the balancing circuit

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify drive parameters related to DC bus configuration and monitoring via the IndraDrive HMI or software.

  2. 2

    Measure incoming AC supply phase-to-phase and phase-to-ground voltages at the drive input terminals to confirm stability, balance, and adherence to specifications.

  3. 3

    Inspect all external DC bus connections (if applicable in multi-axis setups or with external braking units) for proper seating, torque, and signs of damage or corrosion.

  4. 4

    Monitor the overall DC bus voltage and current values using the drive's diagnostic interface to observe for instability or deviations from expected levels under various load conditions.

Browse all codes in this manual (99)
Verified technical data. Last updated: April 2026

Related Faults

F2003Motion step skippedF2004Error in motion profileF2005Cam shaft invalid
Source: Bosch Rexroth IndraDrive MPx02