Danfoss · VLT AutomationDrive FC 301/302
The motor or generator torque has exceeded the configured limit defined in parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode. Parameter 14-25 Trip Delay at Torque Limit can elevate this condition from a warning to an alarm after a set delay.
Click steps to track your progress.
Review parameter 4-16 (Torque Limit Motor Mode) and 4-17 (Torque Limit Generator Mode) settings against application requirements and motor capabilities.
Monitor instantaneous motor torque (e.g., P16-24) during operation to identify when the limit is exceeded.
Inspect the mechanical load for binding, obstructions, or sudden changes in friction that would demand high torque.
Increase acceleration and deceleration ramp times (e.g., P3-41, P3-42) to reduce instantaneous torque demands.
If operating in closed loop, verify encoder feedback integrity (e.g., signal level, proper counts) using drive diagnostics (P16-52).