Danfoss · VLT AutomationDrive FC 301/302
The software installed on the option card in slot A is outdated. This can lead to compatibility problems, missing functionalities, or unstable operation with the main drive software.
Click steps to track your progress.
1. Identify the installed option card in Slot A and determine its current firmware version via the drive's LCP (e.g., P15-06).
2. Verify the compatibility matrix (e.g., from manufacturer website) for the drive's main firmware (P15-05) and the required option card firmware in Slot A.
3. Download the correct, updated firmware file for the option card in Slot A from the manufacturer's support portal.
4. Perform the firmware update procedure for the option card in Slot A using the designated software tool (e.g., MCT 10, USB-to-RS485 adapter) or SD card.
5. After updating, perform a power cycle of the drive and verify the new firmware version is correctly reported (e.g., P15-06).