There is a current leakage from the output phase to ground, which could be located in the cable between the frequency converter and the motor, or within the motor itself. The drive's current transducers detect this by measuring a significant deviation between the output and input currents.
Click steps to track your progress.
Power down the drive and disconnect the motor leads (U, V, W) from the drive's output terminals.
Perform an insulation resistance test (Megger test) on each motor phase to ground (PE) for both the motor cable and the motor windings, checking for values below 1 MOhm.
Inspect the entire length of the motor cable for physical damage, cuts, or signs of water ingress.
Inspect the motor's terminal box for moisture, corrosion, or loose connections that could bridge to ground.
With the motor cable disconnected, power up the drive; if the fault clears, the issue is external (motor/cable).