Danfoss · VLT AutomationDrive FC 301/302
The power transmitted to the brake resistor, calculated as an average over the last 120 seconds, exceeds 90% of its capacity. If option [2] Trip is selected in parameter 2-13 Brake Power Monitoring, the frequency converter trips when dissipated braking power reaches 100%.
Click steps to track your progress.
Monitor the actual brake resistor power dissipation (e.g., via LCP if available) during regenerative operations.
Increase the deceleration ramp time (P3-42 Decel Ramp Time) to spread regenerative energy over a longer period.
Verify the brake resistor's specified continuous power rating and compare it to the application's maximum regenerative power.
Consider upsizing the brake resistor to one with a higher continuous power rating (e.g., from 1kW to 2kW).
Change parameter P2-13 (Brake Power Monitoring) to option [1] Warning to allow continued operation with a warning state.
Check the drive's load profile and cycle time to determine if the application inherently requires a larger resistor.