Danfoss · VLT AutomationDrive FC 301/302
The serial port buffer has overflowed, indicating that data is being received faster than it can be processed. This can lead to loss of communication or corrupted data.
Click steps to track your progress.
Reduce the baud rate of the connected master device to match P8-10 (Baud rate) or a lower, more stable rate.
Verify Parameter P8-11 (Protocol) is correctly configured for the connected device (e.g., FC Protocol, Modbus RTU).
Check the integrity of the serial communication cable for proper shielding and verify termination resistors are correctly installed.
Monitor the communication traffic using a protocol analyzer to identify if an external device is sending excessive data.
Update the drive firmware to the latest available version to address potential communication handler bugs.