Danfoss · VLT AutomationDrive FC 301/302
No motor is connected to the output of the frequency converter. This indicates an open circuit condition on the motor output terminals.
Click steps to track your progress.
Safely de-energize the drive and motor. Verify all physical connections from the drive output (U, V, W) to the motor terminal box.
Measure the resistance between each pair of motor output terminals at the drive (U-V, V-W, W-U); all should be equal and low impedance (e.g., <1 Ohm).
Measure the insulation resistance of the motor windings to ground using a megohmmeter (e.g., 500VDC test, expected >1MOhm).
Disconnect the motor cables from the motor terminal box and measure the resistance of each motor winding (U-V, V-W, W-U) directly at the motor.
Inspect any motor contactor or starter (if present) for proper operation, ensuring all main contacts close when commanded.