Danfoss · VLT AutomationDrive FC 301/302
An option alarm is received, specific to the option. This is most likely caused by a power-up or a communication fault affecting the option card.
Click steps to track your progress.
1. Power down the drive completely and disconnect all input power (L1, L2, L3).
2. Carefully reseat the option card in its designated slot (e.g., Slot A), ensuring it is fully inserted and latched.
3. Verify the drive's main firmware version (P15-05) and the option card's firmware version (P15-06) using the drive's LCP (Local Control Panel).
4. Measure the 24VDC supply voltage at the option card's dedicated power terminals (e.g., X32/1, X32/2) with a multimeter to ensure it is within specified limits (e.g., 22-26VDC).
5. Inspect the option card's connector pins and the drive's slot connector for any signs of physical damage, bent pins, or foreign debris.