EL
ErrorLib
Brands
||
  1. Home
  2. Danfoss
  3. VLT AutomationDrive FC 301/302
  4. 36
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

36

Mains failure

Danfoss · VLT AutomationDrive FC 301/302

What does 36 mean?

This warning/alarm is active when the supply voltage to the drive is lost. It is only issued if parameter 14-10 Mains Failure is not configured to [0] No function.

Common Causes

  • Momentary or sustained loss of one or more phases of the incoming AC supply voltage to the drive (e.g., L1, L2, L3).
  • Tripped upstream circuit breaker or blown fuses in the main distribution panel feeding the drive.
  • Loose or corroded connections at the drive's input power terminals (e.g., L1, L2, L3) causing intermittent contact.
  • Parameter P14-10 (Mains Failure) configured for a sensitive trip threshold (e.g., [1] Warning) leading to nuisance trips.
  • External contactor or switch upstream of the drive opening unexpectedly due to control circuit fault.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify the status of the upstream circuit breaker (e.g., QF1) and fuses in the main power distribution panel.

  2. 2

    2. Measure the incoming AC line-to-line voltages (L1-L2, L2-L3, L3-L1) at the drive's input terminals to confirm stable three-phase supply (e.g., 400VAC ±10%).

  3. 3

    3. Inspect and tighten all power connections at the drive's L1, L2, L3 input terminals using a torque wrench to specified values (e.g., 5 Nm).

  4. 4

    4. Check the setting of parameter P14-10 (Mains Failure) on the drive's LCP; if it's set too sensitively, consider adjusting it to [2] Alarm if appropriate for the application.

  5. 5

    5. Examine the operation of any upstream main contactor (e.g., KM1) and its control circuit for proper engagement and coil voltage (e.g., 110VAC or 24VDC).

Browse all codes in this manual (66)
Verified technical data. Last updated: April 2026

Related Faults

#14Earth (ground) fault#32Motor phase W missing#36Mains failure
Source: Danfoss VLT AutomationDrive FC 301/302
View Official PDFSearch more codes in this manual