4

Mains phase loss

Danfoss · VLT AutomationDrive FC 301/302

What does 4 mean?

A phase is missing on the supply side, or the mains voltage imbalance is too high. This message can also appear if there is a fault in the input rectifier. Options for handling this are programmed in parameter 14-12 Function at Mains Imbalance.

Common Causes

  • Blown fuse or tripped circuit breaker on one of the incoming mains phases (L1, L2, or L3) upstream of the drive.
  • Interruption in the upstream power supply grid causing a complete or partial phase loss.
  • Loose connection or damaged cable on one of the incoming mains phases at the drive's input terminals (e.g., X1:L1).
  • Faulty input rectifier bridge within the drive (e.g., one or more diodes shorted or open).
  • Significant voltage imbalance (e.g., >3%) across the incoming mains phases due to utility issues or heavy unbalanced loads.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the incoming line-to-line voltages (L1-L2, L2-L3, L3-L1) at the drive's input terminals (e.g., X1:L1, X1:L2, X1:L3).

  2. 2

    Check all upstream fuses and circuit breakers (e.g., F1, F2, F3) for continuity and proper operation.

  3. 3

    Inspect all connections of the incoming mains power cables at the drive's input terminals for tightness and corrosion.

  4. 4

    Verify the voltage balance across the incoming phases; ensure no phase deviates by more than 2% from the average phase voltage.

  5. 5

    If an internal rectifier fault is suspected, measure the DC-link voltage (e.g., terminals +DC, -DC) for excessive ripple or asymmetry.

Browse all codes in this manual (66)
Verified technical data. Last updated: April 2026