Danfoss · VLT AutomationDrive FC 301/302
The digital output terminal 29 is experiencing an overload condition. This is likely due to excessive current draw from the connected load or a short-circuit, potentially damaging the output circuitry.
Click steps to track your progress.
Disconnect all external wiring from digital output terminal 29.
Power up the drive and verify if the fault clears; if so, the issue is external to the drive.
With power off, use a multimeter to measure the resistance between terminal 29 and 0V (terminal 33) to check for a short-circuit.
Measure the operating current of the connected load (e.g., contactor coil) using a clamp meter, ensuring it is below the terminal's maximum rating (e.g., 200mA).
Inspect the connected load's wiring for insulation damage or contact with grounded surfaces or other potentials.