Danfoss · VLT AutomationDrive FC 301/302
A digital output on either terminal X30/6 or X30/7 (on MCB 101) is overloaded. This indicates excessive current draw from the connected load or a short-circuit on one of these terminals.
Click steps to track your progress.
Disconnect all external wiring from terminals X30/6 and X30/7 on the MCB 101 board.
Power up the drive and verify if the fault clears; if it does, the issue is external to the drive.
Use a multimeter to measure the resistance between X30/6 and X30/7 to 0V (e.g., terminal X30/8) on the disconnected loads to check for short-circuits.
Measure the current draw of each external load individually (e.g., using a clamp meter) to ensure it is within the rated limits for MCB 101 outputs.
Inspect the wiring connected to X30/6 and X30/7 for insulation breakdown or mechanical damage.